Owner of data set Lapp Norway AS |
Technical purpose ÖLFLEX CLASSIC 110 CY cables are VDE approved power and control cables for occasional flexible use and fixed installation for medium
mechanical load conditions. They are also suitable for use in dry, damp or wet areas.
If using outdoors, observe the indicated temperature range and use with UV protection.
They are largely resistant to acids, alkalis and certain oils at room temperature.
They are suitable for occasional, non-automated movements. The maximum tensile load is 15 N/mm² of conductor cross-section during
installation and operation. Compulsory guidance is not permitted.
The screening braid protects against interference from electrical fields.
Application range:
As power and connecting cable for control systems in machine tools, plant engineering and construction, industrial machin-ery, heating and
air-conditioning systems, conveyor systems, production and assembly lines as well as in measuring and control technology and data
processing systems.
Design
Design based on
EN 50525-2-51
IEC 60227-5
Certification ? VDE-REG 7030 ?
limited to following dimension range:
0.5 mm² - 2.5 mm² 2 - 65 cores
4 mm² - 16 mm² 2 - 7 cores
25 mm² - 120 mm² 2 - 5 cores
EN 13501-6 and EN 50575
Classification of fire behaviour
(article/dimension range see www.lappkabel.com/cpr)
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. EN IEC 60228, Class 5
Insulation PVC compound TI2 acc. to EN 50363-3
with increased requirements acc. to Lapp specification
Core identification code acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers acc. to DIN EN 50334
Cable assembly cores are stranded in layers
Inner sheath PVC compound TM2 acc. to EN 50363-4-1
colour: silver grey, similar RAL 7001
Screen braid of tinned copper, coverage = 85 % (nominal value)
Outer sheath PVC compound TM2 acc. to EN 50363-4-1
colour: transparent |