Owner of data set Lapp Norway AS |
Technical purpose ÖLFLEX CLASSIC 115 CY BK cables are control cables for occasional flexible use and fixed installation under medium mechanical load
conditions. They are also suitable for use in dry, damp or wet areas. They are suitable for outdoor use if the indicated temperature range is
observed. They are largely resistant to acids, alkalis and certain oils at room temperature.
ÖLFLEX CLASSIC 115 CY BK cables are suitable for occasional, non-automated movements. They meet the requirements for slow rotational
movements, such as in the loop of a wind turbine. The maximum tensile load is 15 N/mm² of conductor cross-section during installation and
operation. Compulsory guidance is not permitted.
The screening braid protects against interference from electrical fields.
Application range:
Control units for machine tools, conveyor systems, measurement and control technology, office machines and systems for data processing.
This cable is suitable for torsion application in wind turbines (WTG). The torsional load is limited to applications, as they typically occur in the
loop of a wind turbine. Design based on EN 50525-2-51
Certification EN 13501-6 and EN 50575
Classification of fire behaviour
(article/dimension range see www.lappkabel.com/cpr)
Conductor fine wire strands of bare copper acc. to IEC 60228 resp. EN IEC 60228, class 5
Insulation PVC compound TI2 acc. to EN 50363-3
with increased requirements acc. to Lapp specification
Core identification code acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers acc. to EN 50334
Cable assembly cores are stranded in layers
Wrapping plastic foil
Screen braid of tinned copper, coverage = 85 % (nominal value)
Outer sheath PVC compound TM2 acc. to EN 50363-4-1
with increased requirements acc. to LAPP specification
colour: black, similar RAL 9005 |