Close Go back Collapse all sections
Process Data set: TecFlex H07RN-F 3G2,5 (en) en

Key Data Set Information
Location IT
Geographical representativeness description Nordic
Reference year 2025
Name
TecFlex H07RN-F 3G2,5
Use advice for data set Cradle to Gate. The following stages have been declared: A1-A4
Technical purpose of product or process The Tec Flex H07RN-F cable guarantees a product of great suppleness offering excellent resistance to inclement environmental conditions and to oils & greases as well as adverse mechanical and thermal effects. This makes the product ideal for installation on equipment in continual and interrupted operation under aggressive conditions, (e.g. construction site vehicles, generators, pumps, etc.), as well as most other extreme and severe usage industrial applications. It can be safely be immersed in fresh- or sea water up to100 meters depth and is approved by ”Bureau VERITAS” for ”Marine” applications. This cable is suitable for dry, humid or wet environments in open air, in workshops with an explosive athmosphere. When used for connections they're subjected to medium/severe mechanical stress. It can be used even in fixed laying like floors and temporary construction site set offs.CPR Compliant 305/2011 EU Special Features in addition to the features of the H07RN_F: -Insulation tested up to +90°C. Includes the characteristics of the H07BN4-F cables and the H07BB-F cables. Low Temperature Resistant (-40°C dynamic -50°C static). -AD8 water resistance 10 bar such as the H07RN8-F. -OZONE RESISTANT (Test A) and (Test B). UV Resistant. AG2 Shock Resistant. Excellent resistance to mineral oils, fats, AF3, and atmospheric agents AK2. Resistance to alternate bending of sections ≤ 4 mm2: for at least 100000 cycles General: EN 50525--; ENB 50525-2-21
Classification
Class name : Hierarchy level
  • EPDNorge: Construction / Electronic and electrical components and products
General comment on data set Data quality: Specific data for the product composition are provided by the manufacturer. The data represent the production of the declared product and were collected for EPD development in the year of study. Background data is based on EPDs according to EN 15804 and different LCA databases. The data quality of the raw materials in A1 is presented in the table below. Data from material supplier and the LCA generator has been accepted "As-Is" Data from processing TECCON in-house has been repeated ongoingly without major deviations. Figures given in document are worst case values. Allocation: The allocation is made in accordance with the provisions of EN 15804. Incoming energy and water and waste production in-house is allocated equally among all products through mass allocation. Effects of primary production of recycled materials is allocated to the main product in which the material was used. The recycling process and transportation of the material is allocated to this analysis. The allocation is made in accordance with the guidelines given in EN 15804. Raw material - Information derived from manufactory and from a LCA generator Processing: Derived from actual measurements during production of the individual units/stages Cut-off criteria: All major raw materials and all the essential energy is included. The production processes for raw materials and energy flows with very small amounts (less than 1%) are not included. These cut-off criteria do not apply for hazardous materials and substances. All major materials have been included. Substance representing <1% have not been included. This include folio film for packaging!
Copyright Yes
Owner of data set
Quantitative reference
Reference flow(s)
Biogenic carbon content
  • Carbon content (biogenic): 0.0 kg
  • Carbon content (biogenic) - packaging: 0.009922000008 kg
Time representativeness
Data set valid until 2030
Time representativeness description 2025-04-10 - 2030-04-10
Technological representativeness
Technology description including background system Construction standards: EN 50525--; ENB 50525-2-21 Conductor: Class 5 flexible copper EN60228 Insulation conductor: Elastomer mixture E14 Conductor marking Colored acc. Cenelec Conductor laying SZ Jacket Polycholoprene EM2 Marking H07RN.F xx G YY + Meter marking Voltage - nominal Uo/U 450/750V Voltage - test 2500V Max Conductor temperature operation 90° Max temperature at Short circuit 5s max 250° Resistance insulation 1000M?*Km Resistant to fire performance EN 50265-2-1; EN 60332-1-2 CPR EN 50575 compliance Eca DoP 0270 Temperature - operation -40 to + 90 Temperature - installation -25 + 60 Bending radius 5 x D

Indicators of life cycle

IndicatorDirectionUnit Raw material supply
A1
Transport
A2
Manufacturing
A3
Transport
A4
Installation
A5
Use
B1
Maintenance
B2
Repair
B3
Replacement
B4
Refurbishment
B5
Operational energy use
B6
Operational water use
B7
De-construction
C1
Transport
C2
Waste processing
C3
Disposal
C4
Recycling Potential
D
Input
  • 1.374
  • 0.07516
  • 0.2717
  • 0.007475
  • 0.0348
  • 0
  • 0
  • 0
  • 0
  • 0
  • 1.353
  • 0
  • 0
  • 0.00227
  • 0.0003422
  • 0.003722
  • -10.46
Input
  • 0.3331
  • 0
  • 0
  • 0
  • -0.3265
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
Input
  • 1.707
  • 0.07516
  • 0.2717
  • 0.007475
  • -0.2917
  • 0
  • 0
  • 0
  • 0
  • 0
  • 1.353
  • 0
  • 0
  • 0.00227
  • 0.0003422
  • 0.003722
  • -10.46
Input
  • 8.257
  • 5.377
  • 0.8699
  • 0.5222
  • 0.3092
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.1046
  • 0
  • 0
  • 0.1586
  • 0.01164
  • 0.04201
  • -3.13
Input
  • 5.011
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • -5.011
  • 0
  • 0
Input
  • 13.27
  • 5.377
  • 0.8699
  • 0.5222
  • 0.3092
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.1046
  • 0
  • 0
  • 0.1586
  • -5
  • 0.04201
  • -3.13
Input
  • 0.01218
  • 0
  • 0
  • 0
  • 0.0002442
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.00003086
  • 0.05193
Input
  • 0.04276
  • 0.002674
  • 0.04766
  • 0.0002674
  • 0.001874
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.001063
  • 0
  • 0
  • 0.0000812
  • 0.000009645
  • 0.00008287
  • 0.002888
Input
  • 0.003136
  • 0.009434
  • 0.0002551
  • 0.0009562
  • 0.0003375
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.002648
  • 0
  • 0
  • 0.0002903
  • 0
  • 0.0005042
  • -0.541
Input
  • 0.01001
  • 0.0005618
  • 0.0009289
  • 0.00005584
  • 0.0002382
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.01011
  • 0
  • 0
  • 0.00001696
  • 0.00003288
  • 0.00004775
  • -0.01955
Output
  • 0.004192
  • 0.0002748
  • 0.00008428
  • 0.00002693
  • 0.0001798
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.00006709
  • 0
  • 0
  • 0.000008177
  • 0
  • 0.004412
  • -0.002108
Output
  • 0.153
  • 0.251
  • 0.004056
  • 0.0254
  • 0.03478
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.00805
  • 0
  • 0
  • 0.007711
  • 0
  • 0.1054
  • -0.1243
Output
  • 0.00002741
  • 0.00003666
  • 0.000002364
  • 0.000003557
  • 0.000001404
  • 0
  • 0
  • 0
  • 0
  • 0
  • 9.357E-7
  • 0
  • 0
  • 0.00000108
  • 0
  • 2.141E-7
  • -0.00001003
Output
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
Output
  • 0
  • 0
  • 0.00254
  • 0
  • 0.0009155
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.0432
  • 0.00000535
  • -0.002032
Output
  • 0
  • 0
  • 0.0002898
  • 0
  • 0.02518
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.059
  • 9.1E-7
  • -0.0002676
Output
  • 0
  • 0
  • 0.0004453
  • 0
  • 0.01899
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.1144
  • 0.00001533
  • -0.0006556
Output
  • 0
  • 0
  • 0.006737
  • 0
  • 0.2872
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0
  • 1.731
  • 0.0002319
  • -0.009919

IndicatorUnit Raw material supply
A1
Transport
A2
Manufacturing
A3
Transport
A4
Installation
A5
Use
B1
Maintenance
B2
Repair
B3
Replacement
B4
Refurbishment
B5
Operational energy use
B6
Operational water use
B7
De-construction
C1
Transport
C2
Waste processing
C3
Disposal
C4
Recycling Potential
D
Abiotic depletion potential - fossil resources (ADPF)
  • 12.84
  • 5.377
  • 0.8698
  • 0.5222
  • 0.4007
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.1045
  • 0
  • 0
  • 0.1586
  • 0.01164
  • 0.042
  • -3.131
Abiotic depletion potential - non-fossil resources (ADPE)
  • 0.0001536
  • 0.00000953
  • 4.626E-7
  • 9.54E-7
  • 0.000003301
  • 0
  • 0
  • 0
  • 0
  • 0
  • 5.708E-7
  • 0
  • 0
  • 2.897E-7
  • 6.23E-9
  • 1.7E-8
  • -0.0001682
Acidification potential, Accumulated Exceedance (AP)
  • 0.01732
  • 0.001555
  • 0.0003218
  • 0.00009925
  • 0.0003918
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.00005981
  • 0
  • 0
  • 0.00003014
  • 0.00002229
  • 0.00001596
  • -0.03069
Global Warming Potential - biogenic (GWP-biogenic)
  • -0.02737
  • 0.0001456
  • 0.001043
  • 0.00001429
  • 0.03586
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.0002116
  • 0
  • 0
  • 0.00000434
  • 0.000001439
  • 0.0000019
  • -0.001126
Global Warming Potential - fossil fuels (GWP-fossil)
  • 0.5615
  • 0.3583
  • 0.05959
  • 0.03454
  • 0.02468
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.007654
  • 0
  • 0
  • 0.01049
  • 0.178
  • 0.009915
  • -0.2857
Global Warming Potential - total (GWP-total)
  • 0.5346
  • 0.3586
  • 0.06064
  • 0.03456
  • 0.06056
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.007898
  • 0
  • 0
  • 0.01049
  • 0.178
  • 0.009918
  • -0.2906
Global Warming Potential - land use and land use change (GWP-luluc)
  • 0.0004747
  • 0.0001322
  • 0.00001136
  • 0.00001229
  • 0.00001279
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.00003158
  • 0
  • 0
  • 0.000003732
  • 2.113E-7
  • 6.573E-7
  • -0.003822
  • 0.5582
  • 0.3586
  • 0.06606
  • 0.03456
  • 0.02476
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.007882
  • 0
  • 0
  • 0.01049
  • 0.178
  • 0.01014
  • -0.1947
Eutrophication potential - freshwater (EP-freshwater)
  • 0.0001403
  • 0.000002789
  • 0.000001886
  • 2.759E-7
  • 0.000002914
  • 0
  • 0
  • 0
  • 0
  • 0
  • 5.505E-7
  • 0
  • 0
  • 8.378E-8
  • 1.365E-8
  • 5.321E-8
  • -0.0002104
Eutrophication potential - marine (EP-marine)
  • 0.001229
  • 0.0003374
  • 0.00004158
  • 0.00001964
  • 0.00003524
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.000006574
  • 0
  • 0
  • 0.000005963
  • 0.0000107
  • 0.00001221
  • -0.00151
Eutrophication potential - terrestrial (EP-terrestrial)
  • 0.01764
  • 0.003764
  • 0.000596
  • 0.0002197
  • 0.0004717
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.00008557
  • 0
  • 0
  • 0.0000667
  • 0.0001157
  • 0.00005908
  • -0.02208
Photochemical Ozone Creation Potential (POCP)
  • 0.004987
  • 0.001243
  • 0.0001369
  • 0.00008415
  • 0.0001361
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.00002301
  • 0
  • 0
  • 0.00002555
  • 0.00002771
  • 0.00001782
  • -0.006009
Depletion potential of the stratospheric ozone layer (ODP)
  • 3.299E-8
  • 8.07E-8
  • 8.095E-9
  • 7.823E-9
  • 2.708E-9
  • 0
  • 0
  • 0
  • 0
  • 0
  • 5.25E-10
  • 0
  • 0
  • 2.375E-9
  • 1.36E-10
  • 5.03E-10
  • -0.007661
Water (user) deprivation potential (WDP)
  • 39.48
  • 5.027
  • 9.238
  • 0.5051
  • 1.111
  • 0
  • 0
  • 0
  • 0
  • 0
  • 18.21
  • 0
  • 0
  • 0.1534
  • 0.02637
  • 0.6931
  • -16.26

IndicatorUnit Raw material supply
A1
Transport
A2
Manufacturing
A3
Transport
A4
Installation
A5
Use
B1
Maintenance
B2
Repair
B3
Replacement
B4
Refurbishment
B5
Operational energy use
B6
Operational water use
B7
De-construction
C1
Transport
C2
Waste processing
C3
Disposal
C4
Recycling Potential
D
1This impact category deals mainly with the eventual impact of low dose ionizing radiation on human health of the nuclear fuel cycle. It does not consider effects due to possible nuclear accidents, occupational exposure nor due to radioactive waste disposal in underground facilities. Potential ionizing radiation from the soil, from radon and from some construction materials is also not measured by this indicator.
2The results of this environmental impact indicator shall be used with care as the uncertainties on these results are high or as there is limited experiences with the indicator.
Potential Human exposure efficiency relative to U235 (IRP) 1
  • 0.03059
  • 0.02348
  • 0.002377
  • 0.002282
  • 0.001207
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.001896
  • 0
  • 0
  • 0.000693
  • 0.00001968
  • 0.0002322
  • -0.01233
Potential incidence of disease due to PM emissions (PM) 2
  • 5.106E-8
  • 2.134E-8
  • 1.239E-9
  • 2.114E-9
  • 1.584E-9
  • 0
  • 0
  • 0
  • 0
  • 0
  • 4.29E-10
  • 0
  • 0
  • 6.42E-10
  • 8.7E-11
  • 2.31E-10
  • -1.122E-7
Potential Soil quality index (SQP) 2
  • 5.002
  • 3.632
  • 0.3434
  • 0.3653
  • 0.1936
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.05262
  • 0
  • 0
  • 0.1109
  • 0.001413
  • 0.1257
  • -13.55
Potential Comparative Toxic Unit for humans - non-cancer effects (HTP-nc) 2
  • 2.746E-7
  • 4.332E-9
  • 5.96E-10
  • 4.23E-10
  • 5.651E-9
  • 0
  • 0
  • 0
  • 0
  • 0
  • 5.35E-10
  • 0
  • 0
  • 1.28E-10
  • 1.49E-10
  • 1.19E-10
  • -3.396E-7
Potential Comparative Toxic Unit for humans - cancer effects (HTP-c) 2
  • 3.639E-9
  • 0
  • 2E-11
  • 0
  • 7.4E-11
  • 0
  • 0
  • 0
  • 0
  • 0
  • 2.3E-11
  • 0
  • 0
  • 0
  • 4E-12
  • 3E-12
  • -4.026E-9
Potential Comparative Toxic Unit for ecosystems (ETP-fw) 2
  • 201.4
  • 3.947
  • 0.7649
  • 0.3871
  • 4.574
  • 0
  • 0
  • 0
  • 0
  • 0
  • 0.476
  • 0
  • 0
  • 0.1175
  • 0.03476
  • 21.72
  • -282.5