Process Data set: Medium Voltage air-insulated switchgear UniGear ZS2 Incoming- outgoing feeder 36.12.25 (en) en

Key Data Set Information
Reference year 2024
Name
Medium Voltage air-insulated switchgear UniGear ZS2 Incoming- outgoing feeder 36.12.25
Use advice for data set The life cycle assessment of the UniGear ZS2 IF 36.12.25, an EEPS (Electronic and Electrical Products and Systems), is a “cradle-to-grave” analysis. The figure below shows the product life cycle stages and the information considered in the LCA. In terms of exclusions from the system boundary, according to PCR EPDItaly007, capital goods such as machinery, tools, buildings, infrastructure, packaging for internal transports, and administrative activities, which cannot be allocated directly to the production of the reference product, are excluded. Infrastructures, when present, such as in processes deriving from the ecoinvent database, have not been excluded. Scraps for metal working and plastic processes are also included when already defined in ecoinvent.
Technical purpose of product or process The UniGear ZS2 is the ABB mainline global switchgear in 36kV, 1250A, 25kA which are used in distribution of electric power in a variety of demanding applications such as on off - shore platforms, in container or in a cruise ships, in mines as well as in utility substations, power plants or chemical plants.
Classification
Class name : Hierarchy level
  • EPDNorge: Construction / Electronic and electrical components and products
General comment on data set Both primary and secondary data are used. The main sources for primary data are the bill of materials and technical drawings, while site specific foreground data are provided by ABB. Furthermore, information and data obtained from other LCA studies are also used. For all processes for which primary data are not available, generic data originating from the ecoinvent v3.9.1 database, “allocation, cut-off by classification”, are used. The LCA software used for the calculations is SimaPro 9.5. The utility consumption and waste generation at the ABB manufacturing site is allocated to the production of one UniGear ZS2 IF 36.12.25 by using allocation rules. Natural gas : allocated by surface areas of AIS (Air insulated switchgear) production related buildings. Water : allocated by surface areas of AIS (Air insulated switchgear) production related buildings and allocated per AIS production employees Electricity : allocated by surface areas of AIS (Air insulated switchgear) production related buildings Wastes : allocated by surface areas of AIS (Air insulated switchgear) production related buildings For the end-of-life allocation, the “Polluter Pays” principle is adopted according to what is defined in the CEN/TR 16970 standard, as required by the PCR EPDItaly007. This means, waste treatment processes are allocated to the product system that generates the waste until the end-of-waste state is reached. The environmental burdens of recycling and energy recovery processes are therefore allocated to the product system that generates the waste, while the product system that uses the exported energy and recycled materials receives it burden-free. However, the potential benefits and avoided loads from recovery and recycling processes are not considered because it is not required by EPDItaly007. According to PCR EPDItaly015, the cut-off criteria can be set to a maximum of 2 % of the overall environmental impacts. In this LCA, s connectors, auxiliary switch, label, handle have been excluded as their weights are negligible. Process black oxide and phosphate conversion coating have also been excluded due to the model complexity and unavailability of data.
Copyright Yes
Owner of data set
Quantitative reference
Reference flow(s)
Biogenic carbon content
  • Carbon content (biogenic): 0.0 kg
  • Carbon content (biogenic) - packaging: 0.0 kg
Time representativeness
Data set valid until 2029
Time representativeness description 2024-02-05 - 2029-02-05
Technological representativeness

Indicators of life cycle

IndicatorDirectionUnit Production
A1-A3
Transport
A4
Installation
A5
Use
B1
Waste processing
C3
Input
  • 2.52E+4
  • 22.1
  • 8.81
  • 9.68E+4
  • 143
Input
  • 4.85E+3
  • 0
  • 0
  • 0
  • 0
Input
  • 3E+4
  • 22.1
  • 8.81
  • 9.68E+4
  • 143
Input
  • 8.75E+4
  • 1.43E+3
  • 336
  • 5.04E+5
  • 1.49E+3
Input
  • 2.82E+3
  • 0
  • 0
  • 0
  • 0
Input
  • 9.03E+4
  • 1.43E+3
  • 336
  • 5.04E+5
  • 1.49E+3
Input
  • 383
  • 0
  • 0
  • 0
  • 0
Input
  • 0
  • 0
  • 0
  • 0
  • 0
Input
  • 0
  • 0
  • 0
  • 0
  • 0
Input
  • 85.1
  • 0.203
  • 0.142
  • 394
  • 0.738
Output
  • 1.31
  • 0.00909
  • 0.00188
  • 0.638
  • 0.00564
Output
  • 2.19E+3
  • 69.8
  • 434
  • 1.38E+3
  • 218
Output
  • 0.121
  • 0.000464
  • 0.000174
  • 3.67
  • 0.00289
Output
  • 0
  • 0
  • 0
  • 0
  • 0
Output
  • 132
  • 0
  • 138
  • 0
  • 1E+3
Output
  • 14.8
  • 0
  • 104
  • 0
  • 61.3
Output
  • 26.5
  • 0
  • 246
  • 0
  • 1.3E+2
Output
  • 49.6
  • 0
  • 442
  • 0
  • 233

IndicatorUnit Production
A1-A3
Transport
A4
Installation
A5
Use
B1
Waste processing
C3
Abiotic depletion potential - fossil resources (ADPF)
  • 8.99E+4
  • 1.43E+3
  • 336
  • 5.04E+5
  • 1.49E+3
Abiotic depletion potential - non-fossil resources (ADPE)
  • 1.69
  • 0.000323
  • 0.0000801
  • 0.0436
  • 0.00108
Acidification potential, Accumulated Exceedance (AP)
  • 147
  • 0.414
  • 0.121
  • 1.1E+2
  • 0.617
Global Warming Potential - biogenic (GWP-biogenic)
  • -427
  • 0.0911
  • 1.9E+2
  • 808
  • 78.7
Global Warming Potential - fossil fuels (GWP-fossil)
  • 6.94E+3
  • 1E+2
  • 50.2
  • 2.19E+4
  • 158
Global Warming Potential - total (GWP-total)
  • 6.82E+3
  • 1E+2
  • 2.4E+2
  • 2.28E+4
  • 237
Global Warming Potential - land use and land use change (GWP-luluc)
  • 314
  • 0.0489
  • 0.0144
  • 54.8
  • 0.163
No records found.
No records found.
No records found.
No records found.
No records found.
Eutrophication potential - freshwater (EP-freshwater)
  • 11.4
  • 0.00705
  • 0.00385
  • 2E+1
  • 0.0431
Eutrophication potential - marine (EP-marine)
  • 19.3
  • 0.158
  • 0.492
  • 19.5
  • 0.256
Eutrophication potential - terrestrial (EP-terrestrial)
  • 175
  • 1.69
  • 0.478
  • 172
  • 1.67
Photochemical Ozone Creation Potential (POCP)
  • 60.8
  • 0.606
  • 0.174
  • 55.6
  • 0.522
Depletion potential of the stratospheric ozone layer (ODP)
  • 0.000209
  • 0.00000219
  • 4.61E-7
  • 0.000394
  • 0.00000151
Water (user) deprivation potential (WDP)
  • 2.89E+3
  • 5.79
  • 4.86
  • 5.15E+3
  • 19.7

IndicatorUnit Production
A1-A3
Transport
A4
Installation
A5
Use
B1
Waste processing
C3
1This impact category deals mainly with the eventual impact of low dose ionizing radiation on human health of the nuclear fuel cycle. It does not consider effects due to possible nuclear accidents, occupational exposure nor due to radioactive waste disposal in underground facilities. Potential ionizing radiation from the soil, from radon and from some construction materials is also not measured by this indicator.
2The results of this environmental impact indicator shall be used with care as the uncertainties on these results are high or as there is limited experiences with the indicator.
Potential Human exposure efficiency relative to U235 (IRP) 1
  • 0
  • 0
  • 0
  • 0
  • 0
Potential incidence of disease due to PM emissions (PM) 2
  • 0
  • 0
  • 0
  • 0
  • 0
Potential Soil quality index (SQP) 2
  • 0
  • 0
  • 0
  • 0
  • 0
Potential Comparative Toxic Unit for humans - non-cancer effects (HTP-nc) 2
  • 0
  • 0
  • 0
  • 0
  • 0
Potential Comparative Toxic Unit for humans - cancer effects (HTP-c) 2
  • 0
  • 0
  • 0
  • 0
  • 0
Potential Comparative Toxic Unit for ecosystems (ETP-fw) 2
  • 0
  • 0
  • 0
  • 0
  • 0