Process Data set: COMPACT SECONDARY SUBSTATION: UniPack-S Mercury 25NS 2250/2500kVA 22kV/433V, AN/AF (en) en

Key Data Set Information
Location CH
Geographical representativeness description Europe
Reference year 2025
Name
COMPACT SECONDARY SUBSTATION: UniPack-S Mercury 25NS 2250/2500kVA 22kV/433V, AN/AF
Use advice for data set The life cycle assessment is a “cradle-to-grave” analysis, and the system boundaries are defined according to EN 50693, as required by the PCR. For transparency reasons, the manufacturing stage is further divided into an upstream and core stage.
Technical purpose of product or process This Environmental Product Declaration is a specific product EPD, and the declared product is the compact secondary substation: UniPack-S Mercury 25NS 2250/2500kVA 22kV/433V, AN/AF including related accessories and packaging. The constituent materials of compact secondary substation: UniPack-S Mercury 25NS 2250/2500kVA 22kV/433V, AN/AF are presented below. Type Material Weight [kg] Weight % Metals Steel 6311.6 54.9% Aluminium 1738.9 15.1% Stainless steel 1 007.5 8.8% Other steels 842.4 7.3% Copper 607.6 5.3% Other metals 12.1 0.1% Plastics Epoxy Resin 721.5 6.3% Other plastics 120.2 1 % Others Rubber 9.5 <1% Electric components 3.1 <1% SF6 3.1 <1% Other 117.4 1% Total 11 494.61 100%
Classification
Class name : Hierarchy level
  • EPDNorge: Construction
General comment on data set Both primary and secondary data are used. The main sources for primary data are the bill of materials, technical drawings, and site-specific foreground data provided by ABB. For all processes for which primary data are not available, generic background data originating from the ecoinvent v3.9.1 database, with system model “allocation, cut-off by classification”, are used. The LCA software used for the calculations is SimaPro 9.5. The utility consumption and waste generation by ABB, in the core manufacturing stage, is allocated to the production of one reference product according to applicable rules. For the end-of-life allocation, the “Polluter Pays” principle is adopted according to what is defined in the CEN/TR 16970 standard. However, the potential benefits and avoided loads from recovery and recycling processes are not considered because it is not required by the PCR. According to PCR or Standard, the cut-off criteria can be set to a maximum of 2 % of the overall environmental impacts. In this LCA, several electrical materials which constitute less than 2% of the total weight have been excluded as their weights are negligible
Copyright Yes
Owner of data set
Quantitative reference
Reference flow(s)
Biogenic carbon content
  • Carbon content (biogenic): 0.0 kg
  • Carbon content (biogenic) - packaging: 0.0 kg
Time representativeness
Data set valid until 2030
Time representativeness description 2025-05-27 - 2030-05-27
Technological representativeness
Technology description including background system General technical information of the compact secondary substation: UniPack-S Mercury 25NS 2250/2500kVA 22kV/433V, AN/AF are presented below. Description Device Code 1 Ratings Enclosure N42 storm grey, Galvanized steeI 2mm thickness for main parts corrosivity category: C4 acc. to ISO12944-6 MV Switchgear RMU_SafePlus CV20C 630A 24kV 21kA/3s Dry Transformer 2250/2500kVA 22/0.433kV AN/AF cast coil dry transformer Dyn11 Low Voltage Switchboard Unipack LVS3-IEC 61439-1: 4000A 433V 50kA/s 50Hz RTU RTU 530 Size Width 2.44 m Height 2.861 m Depth 4.767 m Weight 11 494.61 kg Ratings Nominal voltage 22kV/0.433kV Rated current [A] MV:630A LV: 4000A Rated Short circuit withstand [kA] MV: 21kA/3s LV: 50kA/1s Rated implulse withstand voltage 125 kV Rated insulation voltage 50 kV Rated Frequency 50 Hz Protection class MV compartment: IP54 LV compartment: IP54 DCS compartment: IP54 Transformer compartment: IP45 Compact secondary substation: UniPack-S Mercury25NS 2250/2500kVA 22kV/433V, AN/AF is manufactured by ABB Automation and Electrification (Vietnam) Ltd located in Lot C3,Road TS3 Tien Son IZ Tu Son Town, Bac Ninh, Vietnam. The manufacturing site is certified according to the following standards: - ISO 9001:2015 – Quality Management Systems - ISO 14001:2015 – Environmental Management Systems -ISO 45001:2018 – Occupational Health and Safety Management Systems

Indicators of life cycle

IndicatorDirectionUnit Production
A1-A3
Transport
A4
Installation
A5
Use
B1
Waste processing
C3
Input
  • 1.22E+5
  • 157
  • 102
  • 3.2E+6
  • 1.4E+3
Input
  • 2.22E+4
  • 0
  • 0
  • 0
  • 0
Input
  • 1.44E+5
  • 157
  • 102
  • 3.2E+6
  • 1.4E+3
Input
  • 8.84E+5
  • 1.82E+4
  • 7.94E+3
  • 4.62E+7
  • 1.35E+4
Input
  • 7.3E+3
  • 0
  • 0
  • 0
  • 0
Input
  • 8.93E+5
  • 1.82E+4
  • 7.94E+3
  • 4.62E+7
  • 1.35E+4
Input
  • 4.6E+3
  • 0
  • 0
  • 0
  • 0
Input
  • 0
  • 0
  • 0
  • 0
  • 0
Input
  • 0
  • 0
  • 0
  • 0
  • 0
Input
  • 551
  • 1.77
  • 1
  • 8.62E+3
  • 6.92
Output
  • 62.9
  • 0.0978
  • 0.0512
  • 46.7
  • 0.0495
Output
  • 2.27E+4
  • 2.7E+2
  • 413
  • 1.66E+5
  • 1.77E+3
Output
  • 1.08
  • 0.00245
  • 0.00163
  • 2.07
  • 0.023
Output
  • 0
  • 0
  • 0
  • 0
  • 0
Output
  • 2.16E+3
  • 0
  • 0
  • 0.184
  • 8.62E+3
Output
  • 395
  • 0
  • 551
  • 0
  • 94.8
Output
  • 8.5E+2
  • 0
  • 1.22E+3
  • 0
  • 153
Output
  • 1.53E+3
  • 0
  • 2.2E+3
  • 0
  • 275

IndicatorUnit Production
A1-A3
Transport
A4
Installation
A5
Use
B1
Waste processing
C3
Abiotic depletion potential - fossil resources (ADPF)
  • 9E+5
  • 1.82E+4
  • 7.94E+3
  • 4.62E+7
  • 1.35E+4
Abiotic depletion potential - non-fossil resources (ADPE)
  • 8.04
  • 0.00216
  • 0.0018
  • 4.61
  • 0.00852
Acidification potential, Accumulated Exceedance (AP)
  • 807
  • 34
  • 2.53
  • 2.26E+4
  • 6.04
Global Warming Potential - biogenic (GWP-biogenic)
  • 671
  • 2.3
  • 807
  • 1.32E+4
  • 102
Global Warming Potential - fossil fuels (GWP-fossil)
  • 7.43E+4
  • 1.43E+3
  • 564
  • 4.43E+6
  • 1.34E+3
Global Warming Potential - total (GWP-total)
  • 7.54E+4
  • 1.44E+3
  • 1.37E+3
  • 4.44E+6
  • 1.44E+3
Global Warming Potential - land use and land use change (GWP-luluc)
  • 124
  • 1.02
  • 0.292
  • 545
  • 1.78
No records found.
No records found.
No records found.
No records found.
No records found.
Eutrophication potential - freshwater (EP-freshwater)
  • 58.9
  • 0.0643
  • 0.0488
  • 7.12E+3
  • 0.366
Eutrophication potential - marine (EP-marine)
  • 97.4
  • 8.68
  • 0.953
  • 4.97E+3
  • 1.85
Eutrophication potential - terrestrial (EP-terrestrial)
  • 1.12E+3
  • 95.8
  • 1E+1
  • 4.04E+4
  • 15.1
Photochemical Ozone Creation Potential (POCP)
  • 351
  • 26.3
  • 3.41
  • 1.11E+4
  • 4.65
Depletion potential of the stratospheric ozone layer (ODP)
  • 0.00174
  • 0.000022
  • 0.00000901
  • 0.0257
  • 0.0000257
Water (user) deprivation potential (WDP)
  • -3.11E+4
  • 51.8
  • 28.4
  • 2.93E+5
  • 201

IndicatorUnit Production
A1-A3
Transport
A4
Installation
A5
Use
B1
Waste processing
C3
1This impact category deals mainly with the eventual impact of low dose ionizing radiation on human health of the nuclear fuel cycle. It does not consider effects due to possible nuclear accidents, occupational exposure nor due to radioactive waste disposal in underground facilities. Potential ionizing radiation from the soil, from radon and from some construction materials is also not measured by this indicator.
2The results of this environmental impact indicator shall be used with care as the uncertainties on these results are high or as there is limited experiences with the indicator.
Potential Human exposure efficiency relative to U235 (IRP) 1
  • 0
  • 0
  • 0
  • 0
  • 0
Potential incidence of disease due to PM emissions (PM) 2
  • 0
  • 0
  • 0
  • 0
  • 0
Potential Soil quality index (SQP) 2
  • 0
  • 0
  • 0
  • 0
  • 0
Potential Comparative Toxic Unit for humans - non-cancer effects (HTP-nc) 2
  • 0
  • 0
  • 0
  • 0
  • 0
Potential Comparative Toxic Unit for humans - cancer effects (HTP-c) 2
  • 0
  • 0
  • 0
  • 0
  • 0
Potential Comparative Toxic Unit for ecosystems (ETP-fw) 2
  • 0
  • 0
  • 0
  • 0
  • 0