| Key Data Set Information | |
| Location | NO |
| Geographical representativeness description | Nordic |
| Reference year | 2025 |
| Name |
|
| Use advice for data set | Cradle to Gate. The following stages have been declared: A1-A4 |
| Technical purpose of product or process | Pre-wired corrugated, pliable self-recovering conduit acc. to EN 61386-1 and EN 61386-22. X-Flame halogen-free fire resistant cable designed for installation in places wher it is required to ensure operation ofdevice under fire conditions. Primary in use at lighting installations, smoke extraction-, alarm-, signaling-, sound warning- and control systems, fire alarm and automation and other safety ensuring circuits. (NS3960:2018 sec. 8.3). ””S”” version - statict screen protect against interferences og magnetic fields. Cable will under fire stay in operation = 180min. CONDUIT Construction standards EN 611386-1; EN 61386-22 ICTA 34423 Cable Factory standard CABLE Construction - Factory standard |
| Classification |
Class name
:
Hierarchy level
|
| General comment on data set | Data quality: Specific data for the product composition are provided by the manufacturer. The data represent the production of the declared product and were collected for EPD development in the year of study. Background data is based on EPDs according to EN 15804 and different LCA databases. The data quality of the raw materials in A1 is presented in the table below. Data from material supplier and the LCA generator has been accepted "As-Is" Data from processing TECCON in-house has been repeated ongoingly without major deviations. Figures given in document are worst case values. Allocation: The allocation is made in accordance with the provisions of EN 15804. Incoming energy and water and waste production in-house is allocated equally among all products through mass allocation. Effects of primary production of recycled materials is allocated to the main product in which the material was used. The recycling process and transportation of the material is allocated to this analysis. The allocation is made in accordance with the guidelines given in EN 15804. Raw material - Information derived from manufactory and from a LCA generator Processing: Derived from actual measurements during production of the individual units/stages. Cut-off criteria: All major raw materials and all the essential energy is included. The production processes for raw materials and energy flows with very small amounts (less than 1%) are not included. These cut-off criteria do not apply for hazardous materials and substances. All major materials have been included. Substance representing <1% have not been included. This include folio film for packaging! |
| Copyright | Yes |
| Owner of data set | |
| Quantitative reference | |
| Reference flow(s) |
|
| Biogenic carbon content |
|
| Time representativeness | |
| Data set valid until | 2030 |
| Time representativeness description | 2025-05-07 - 2030-05-07 |
| Technological representativeness | |
| Technology description including background system | Corrugated Conduit Pliable/Self recovering halogen free Polypropylene Compression force 750N Marking EN, Date, and meter marking: 0-100m Temperature - operation -25 to + 90°C Temperature - installation -5 to + 90°C Bending Radius 8 x D Resistant to fire performance Flame retardant, self-extinguishing, low smoke toxic emission Insulations resistance >100M? at 500V in 1 min Test - mechanical Acc. EN 61386-1; EN 61386-22 Test - electrical Acc. EN 61386-1; >2,0kV 50HZ in 15 min CABLE Construction standards Factory standard Conductor Bare, solid copper. EN60228 class 1 Insulation - conductor Special ceramic silicone rubber Conductor marking Color code - Blue, Brown Conductor laying Twisted Screen Aluminium backed poluester tape with tinned copper drain wire Jacket Halogen-free compound - Color red Marking Bitflame S FE180/E90 Voltage - nominel Uo/U 300/500V Voltage - test AC: 2000V; DC: 5000V Max Conductor temperature 70° 250° Resistance isulation 100MOxKm Resistant to fire performance EN60332-1; EN60332-3-22; EN60332-3A Corrosive gas and Smoke EN 602754-2; EN61034-2 Resistance during fire EN60331-11; EN60331-21; EN60331-23; EN50200 Temperature - operation -40° to 80°C Temperature - installation minimum -10°C Bending radius 8 x OD |
| Subtype | specific dataset | ||||
| LCA methodology report | |||||
| Data sources, treatment and representativeness | |||||
| Documentation of data quality management | |||||
| Data source(s) used for this data set | |||||
| Completeness | |||||
| Validation | |||||
| |||||
| Compliance Declarations | |||||
| Compliance |
Compliance system name
EN 15804+A2
|
Approval of overall compliance
Fully compliant |
Nomenclature compliance
Fully compliant |
Methodological compliance
Fully compliant |
Review compliance
Fully compliant |
Documentation compliance
Fully compliant |
Quality compliance
Fully compliant |
| Compliance |
Compliance system name
|
Approval of overall compliance
Fully compliant |
Nomenclature compliance
Fully compliant |
Methodological compliance
Fully compliant |
Review compliance
Fully compliant |
Documentation compliance
Fully compliant |
Quality compliance
Fully compliant |
| Compliance |
Compliance system name
|
Approval of overall compliance
Fully compliant |
Nomenclature compliance
Fully compliant |
Methodological compliance
Fully compliant |
Review compliance
Fully compliant |
Documentation compliance
Fully compliant |
Quality compliance
Fully compliant |
| Data generator | |
| Data set generator / modeller |
|
| Data entry by | |
| Time stamp (last saved) | 2025-06-27T12:39:00 |
| Data set format(s) | |
| Publication and ownership | |
| UUID | ee6521ba-dfe2-4c7b-ab7f-4054794c6860 |
| Date of last revision | 2025-05-06T08:38:16.2264845Z |
| Data set version | 00.03.000 |
| Registration authority | |
| Registration number | NEPD-9988-9925 |
| Owner of data set | |
| Copyright | Yes |
| License type | Free of charge for all users and uses |
| Access and use restrictions | None |
Indicators of life cycle